Seeking feedback on 23 October 2025 under-frequency event
- Transmission
- Compliance
The Electricity Authority Te Mana Hiko is seeking feedback from electricity market participants who may have been substantially affected by an under-frequency event on 23 October 2025.
An under-frequency event occurs when the system frequency falls below 49.25Hz.
On 23 October 2025, at approximately 5.42pm, circuit breaker 662 at Wairakei was closed, energising circuit TAB-WRK-1. Circuit breaker 662 (CB662) at Tauhara was then closed. Within seconds, the Tauhara geothermal unit (TAB G1) and Te Huka 3 geothermal unit (TAC G1) both tripped. The resulting imbalance between generation and demand caused the North Island frequency to fall to a minimum of 49.2Hz. Automatic reserves responded and rebalanced the power system, returning frequency to the normal operating band by 5.43pm.
The Authority’s draft determination is that the System Operator caused this under-frequency event. Our reasons are outlined in this draft determination paper.
Feedback is welcomed on our draft determination by 5pm, 31 August 2026 to compliance@ea.govt.nz
We will consider all submissions before making our final decision.
Related News
New operators approved for Type B co-generating stations
The Electricity Authority Te Mana Hiko has approved applications from New Zealand Steel Limited and Whareroa Cogeneration Limited to operate plants at Glenbroo…
Retailers asked to complete readiness survey on October Code amendments
The Electricity Authority is seeking information about electricity retailers’ readiness for amendments to the Electricity Industry Participation Code 2010 that…
Decision on 4 February 2026 under-frequency event
An under‑frequency event occurred at approximately 8.29pm on 4 February 2026 when HVDC Pole 3 suddenly ramped down, reducing North Island frequency to 49.20Hz.